Response spectrum range | 4.3μm, 5.0μm, 185~260nm |
Detection object | Flame |
Detection method | Real-time sampling of optical path |
Display method | LED lights |
Status indication | Green LED flashes to indicate normal operation (the number of flashes every 3 seconds represents the sensitivity level) Red LED always lights to indicate an alarm |
Operation method | Magnetic bar to adjust sensitivity (4 levels totally) |
Signal output | 4-20mA output 2 relays for fault and alarm (free contact) |
Response time | <30s |
Ex grade | Ex d IIC T6 Gb / Ex tD A21 |
Ingress protection | IP66 |
Supply voltage | DC24V±6V |
Working current | ≤30mA (DC23V) |
Longest detection distance | 50 meters, 0.3m×0.3m N-heptane fire |
Field of view | IR sensors: 90° UV sensor: 120° |
Weight | 1.5±0.2kg |
Installation method | Wall mounted or lifting or holding-pipe |
Cable entry interface | NPT1/2, default transfer to G1/2 (internal thread) |
Housing material | Copper-free cast aluminum (epoxy resin on the surface) |
Environment temp | -20℃~+60℃ |
Environment humidity | ≤95%RH (no condensation) |